MI 3152 EUROTEST XC

Measuring functions

  • Insulation resistance with DC voltage from 50 V to 1000 V;
  • Varistor test;
  • Continuity of PE conductors with 200 mA DC test current with polarity change;
  • Continuity of PE conductors with 7 mA test current without RCD tripping;
  • Line/Loop impedance combined also in one function Z AUTO;
  • Loop impedance with Trip Lock RCD function;
  • TRMS voltage and frequency measurements;
  • Phase sequence;
  • Power and THD measurement (up to the 12th harmonic);
  • RCD testing (general and selective, type AC, A, F, B, B+, MI RCD, EV RCD, PRCD, PRCD-K, PRCD-S);
  • Earth resistance (3-wire and 2-clamps method);
  • Specific earth resistance with Ro-adapter (option);
  • TRMS leakage and load currents (option);
  • First fault leakage current (ISFL);
  • Testing of Insulation Monitoring Devices (IMDs);
  • Illumination (option);
  • High resolution Loop impendance (mΩ) (option);
  • EVSE AUTO SEQUENCEs and function inspections;
  • Determining location of cables (option);
  • QR and/or barcode scanner support (option).

Key features

  • Predefined profile dependent
  • AUTO SEQUENCEs.
  • Predefined Automatic tests: 
        Auto TT (U, Zln, Zs, Uc); 
        Auto TN/RCD (U, Zln, Zs, Rpe); 
        Auto TN (U, Zln, Zlpe, Rpe); 
        Auto IT (U, Zln, Isc, Isfl, IMD).
  • Built-in help screens for referencing on site.
  • Built-in fuse tables for automatic evaluation of the line / loop impedance result.
  • Monitoring of all 3 voltages in real-time.
  • Automatic polarity reversal on continuity test.
  • Automated RCD testing procedure.
  • Automated Impedance testing procedure (Z AUTO).
  • Functional inspections.
  • Measurement filtering according  to the selected area group.
  • Built-in charger and rechargeable batteries as standard accessory.
  • BT communication with PC, Android tablets and smart phones via built-in BT.
  • PC SW Metrel ES Manager (structure and report creation, data upload/download).
  • Optional aMESM Android APP (structure and report creation, data upload/download).

Technical data

  • Dimensions (w x h x l): 230 x 103 x 115 mm.
  • Mass (without accessories): 1.3 kg.

  • Share on

MI 3152 EurotestXC is an instrument from the new generation of Metrel’s multifunctional measuring instruments. The already well known functions like complete installation safety testing according to IEC/EN 61557 and AUTO SEQUENCE testing of TN, TT and IT earthing systems are managed by a completely new user interface based on large colour touch screen display. A wide range of functions is included: from on-line voltage monitoring, phase sequence testing, varistor testing, earth resistance measurement, illuminance measurement and TRMS current measurement up to RCD tests, line and loop impedance tests, specific earth resistance measurements as well as ISFL measurements and the IMD tests.

ket Function is supported
ket F unction is not supported
ket Function is optional

 


MI 3152 EurotestXC

 

 

 

 

 

 

Extra Features Workspaces El. LV Installation Safety Modes
Industrial Mode
Medical Mode
EVSE Mode
IT Vehicles / Mobile Units Mode
Lightning Mode
Project Structure
Visual Inspection Mode
Functional Inspection Mode
AUTOSEQUENCE ® AUTOSEQUENCE profile
AUTOSEQUENCE EVSE
PASS/FAIL System Evaluation
AUTOSEQUENCE Barcode testing
Advanced User Interface Colour display
Touch screen
Adaptable user interface
Graphical Help Menus
Database System Built In
Programmable Memory Structure
Multi-level Memory Organiser
On-site Parameter Settings
Auto Test AUTO IT (U, Zln, Isc, Isfl, IMD)
AUTO TN (U, Zln, Zlpe, Rpe)
AUTO TN/RCD (U, Zln, Zs, Rpe)
AUTO TT (U, Zln, Zs, Uc)
Automatic test sequence Multitest sequence
Main Features Voltage Frequency
Voltage Monitoring
Voltage TRMS
Three Phase 3-Phase system (Phase SEQUENCE)
Differential leakage current
Insulation Resistance Test Voltage 50 V
Test Voltage 100 V
Test Voltage 250 V
Test Voltage 500 V
Test Voltage 1000 V
Test of IMD
Test of ELM
Automatic Discharge
DC Ramp Voltage Test/Varistor test
Leakage Current Differential Leakage
Leakage Current (with optional Clamp)
ISFL: L1,L2 (First Fault Leakage)
AC Insulation Leakage
Z Line / Loop Impedance Autotest TN/TT Z L-N, L-PE, dU, Uc
Zline L-L, L-N Ipsc - 3 Wire
Zloop L-PE, Ipfc - 3 Wire
Zs (rcd) - 3 Wire
Zref, ΔU%
Fuse Tables
Max. Ipfc = 20kA
RCD RCD type AC
RCD type A
RCD type F
RCD type B
RCD type B+
RCD Uc
RCD I Ramp
RCD Auto
RCD 3-Phase
EV-RCD
MI-RCD
RCD-S (Selective)
RCD (t)
PRCD PRCD-S , PRCD-K
ELR industrial RCD Earth (Electric) Leakage Relay
Earth / Ground Resistance Earth Resistance 2-wire
Earth Resistance 3-wire
Two Iron Clamps Earth Resistance
Wenner 4-wire Specific Earth Resistance
Functional Load test
Power Measurements Active power
Reactive power
Apparent power
Power factor
Harmonics Analysis THD current
THD voltage
Current harmonics
Voltage harmonics
Microclimatic Measurements Illuminance
Additional Features Hand-Held Hand-Held
Display LCD
Back Light
PASS / FAIL Indicators PASS / FAIL Indicators
Buzzer Buzzer
Mains Supply / PE Check Mains Supply / PE Check
Keyboard QWERTY Keyboard
Connectivity Communication Port USB
Built-in Bluetooth
Android Application
Communication Port RS232 - PS/2
Memory Downloadable
Internal memory
microSD memory card
Uploadable
Printing and scanning QR-Code Printing / Scanning
Cable location Cable location
Security User Accounts
Power Supply Battery Powered
Rechargeable Batteries in standard delivery
Graphical user interface Graphical user interface
Special Accessories Battery Charger Battery Charger
Pasive 3-Phase Adapter Pasive 3-Phase Adapter
Active Euro Checkbox Active Euro Checkbox
Active Ring Adapter EASYswitch Active Ring Adapter EASYswitch (UK only)
Tip Commander Tip Commander
Plug Commander Plug Commander
PC Software Package MESM Compatible
Report creation
PC Software Package
Professional reporting
Adapter for specific resistance ρ ρ adapter
Cable Locator Cable Locator
Current clamps DC - Current Clamp
Generator Current Clamp
AC Leakage Current Clamp
Environment measurements Lux Sensor
Connectivity accessories Smart phones scanner
Standards Applied IEC 60364 IEC 60364-6
IEC 60364-4-41
IEC 60755 IEC 60755
IEC 61008 IEC 61008
IEC 61009 IEC 61009
IEC 61557 IEC 61557-1
IEC 61557-2
IEC 61557-3
IEC 61557-4
IEC 61557-5
IEC 61557-6
IEC 61557-7
IEC 61557-10
IEC 61557-12
IEC 61557-14
AS / NZ 3760 AS / NZ 3760
AS / NZ 3018 AS / NZ 3018
AS / NZ 3017 AS / NZ 3017
VDE 0413 VDE 0413
VDE 0100 VDE 0100
HD 384 HD 384
BS 7671 BS 7671 17th Edition