The GWInstek PSU-Series is a single output programmable switching DC power supply covering a power range up to 1520W. This Series of products include five models with the combination from 6V to 60V rated voltages. As th ePSU-series can be connected in series for maximum 2 units or in parallel for maximum 4 units, capacity of connecting multiple PSU-Series units for higher voltage or higher current output provides a broad coverage of applications.
The C.V / C.C priority selection of the PSU-Series is a very useful features for DUT protection. The conventional power supply normally operates under C.V mode when the power supply is turned on. This could bring a high inrush current to the capacitive load or current-intensive load at the power output on stage. Though the current becomes stable after the C.C mode is activated, the current spike occurred at the C.V and C.C crossover point may possibly damage the DUT. At the power output on stage, the PSU-Series is able to run under C.C priority to limit the current spike occurred at the threshold voltage and therefore protects DUT from the inrush current damage. The OVP and OCP protections can prevent the DUT damage. Both OVP and OCP levels can be selected the range of 10% to 110%, with the default level set at 110%, of the rated voltage / current of the power supply. THe PSU-Series provides USB Host / Device , LAN, RS-232 with RS-485 and Analog Control Interfaces as standard. The LabView driver is available at the rear panel for external control of the power On/ Off and the external monitoring of the power output voltagre and current.
Ordering Info :
PSU 12.5-120 |
PSU 20-76 |
PSU 40-38 |
PSU 60-25 |
PSU 6-200 |
PSU 100-15 1500W Programmable Switching DC Power Supply |
PSU 150-10 1500W Programmable Switching DC Power Supply |
PSU 300-5 1500W Programmable Switching DC Power Supply |
PSU 400-3.8 1520W Programmable Switching DC Power Supply |
PSU 600-2.6 1560W Programmable Switching DC Power Supply |
Output |
|||||||
Model |
|
PSU |
6-200 |
12.5-120 |
20-76 |
40-38 |
60-25 |
Rated Output Voltage (*1) |
|
V |
6 |
12.5 |
20 |
40 |
60 |
Rated Output Current (*2) |
|
A |
200 |
120 |
76 |
38 |
25 |
Rated Output Power |
|
W |
1200 |
1500 |
1520 |
1520 |
1500 |
Constant Voltage Mode |
|||||||
Model |
|
PSU |
6-200 |
12.5-120 |
20-76 |
40-38 |
60-25 |
Line regulation (*3) |
|
mV |
2.6 |
3.25 |
4 |
6 |
8 |
Load regulation (*4) |
|
mV |
2.6 |
3.25 |
4 |
6 |
8 |
Ripple and noise (*5) |
p-p (*6) |
mV |
60 |
60 |
60 |
60 |
60 |
|
r.m.s. (*7) |
mV |
8 |
8 |
8 |
8 |
8 |
Temperature coefficient |
|
ppm/ °C |
100ppm/°C of rated output voltage, after a 30 minute warm-up. |
||||
Remote sense compensation voltage (single wire) |
|
V |
1 |
1 |
1 |
2 |
3 |
Rise time (*8) |
Rated load |
ms |
80 |
80 |
80 |
80 |
80 |
|
No load |
ms |
80 |
80 |
80 |
80 |
80 |
Fall time (*9) |
Rated load |
ms |
10 |
50 |
50 |
80 |
80 |
|
No load |
ms |
500 |
700 |
800 |
1000 |
1100 |
Transient response time (*10) |
|
ms |
1.5 |
1 |
1 |
1 |
1 |
Constant Current Mode |
|||||||
Model |
|
PSU |
6-200 |
12.5-120 |
20-76 |
40-38 |
60-25 |
Line regulation (*3) |
|
mA |
22 |
14 |
9.6 |
5.8 |
4.5 |
Load regulation (*11) |
|
mA |
45 |
29 |
20.2 |
12.6 |
10 |
Ripple and noise (*12) |
r.m.s. |
mA |
400 |
240 |
152 |
95 |
75 |
Temperature coefficient |
|
ppm/ °C |
100ppm/°C of rated output voltage, after a 30 minute warm-up. |
||||
Protection Function |
|||||||
Model |
|
PSU |
6-200 |
12.5-120 |
20-76 |
40-38 |
60-25 |
Over voltage protection (OVP) |
Setting range |
V |
0.6-6.6 |
1.25-13.75 |
2-22 |
4-44 |
5-66 |
|
Setting accuracy |
V |
0.06 |
0.125 |
0.2 |
0.4 |
0.6 |
Over current protection (OCP) |
Setting range |
A |
5-220 |
5-132 |
5-83.6 |
3.8-41.8 |
2.5-27.5 |
|
Setting accuracy |
A |
4 |
2.4 |
1.52 |
0.76 |
0.5 |
Under voltage limit (UVL) |
Setting range |
|
0-6.3 |
0-13.12 |
0-21 |
0-42 |
0-63 |
Over temperature protection (OHP) |
Operation |
|
Turn the output off. |
||||
Incorrect sensing connection protection (SENSE) |
Operation |
|
Turn the output off. |
||||
Low AC input protection (AC-FAIL) |
Operation |
|
Turn the output off. |
||||
Shutdown (SD) |
Operation |
|
Turn the output off. |
||||
Power limit (POWER LIMIT) |
Operation |
|
Over power limit. |
||||
|
Value (fixed) |
|
Approx. 105% of rated output power |
||||
Analog Programming and Monitoring |
|||||||
Model |
|
PSU |
6-200 |
12.5-120 |
20-76 |
40-38 |
60-25 |
External voltage control output voltage |
|
|
Turn the output off. |
||||
External voltage control output current |
|
|
Turn the output off. |
||||
External resistor control output voltage |
|
|
Turn the output off. |
||||
External resistor control output current |
|
|
Turn the output off. |
||||
Output voltage monitor |
|
|
Turn the output off. |
||||
Output current monitor |
|
|
Turn the output off. |
||||
Shutdown control |
|
|
Turns the output off with a LOW (0V to 0.5V) or short-circuit. |
||||
Output on/off control |
|
|
Possible logic selections: |
||||
Alarm clear control |
|
|
Clear alarms with a LOW (0V to 0.5V) or short-circuit. |
||||
CV/CC/ALM/PWR ON/OUT ON indicator |
|
|
Photocoupler open collector output; Maximum voltage 30V, maximum sink current 8mA. |
||||
Trigger out |
|
|
Maximum low level output = 0.8V; minimum high level output = 2V; Maximum source current = 8mA. |
||||
Trigger in |
|
|
Maximum low level input voltage = 0.8V; minimum high level input votage = 2.0V, Maximum sink current = 8mA. |
||||
Front Panel |
|||||||
Model |
|
PSU |
6-200 |
12.5-120 |
20-76 |
40-38 |
60-25 |
Display, 4 digits |
|
|
|
|
|
|
|
Voltage accuracy |
0.1% + |
mV |
12 |
25 |
40 |
80 |
120 |
Current accuracy |
0.2% + |
mA |
600 |
360 |
228 |
114 |
75 |
Indications |
|
|
GREEN LED's: CV, CC, V, A, VSR, ISR, DLY, RMT, LAN, M1, M2, M3, RUN, Output ON |
||||
Buttons |
|
|
Lock/Local(Unlock), PROT(ALM_CLR), Function(M1), Test(M2), Set(M3), Shift, Output |
||||
Knobs |
|
|
Voltage, Current |
||||
USB port |
|
|
Type A USB connector |
||||
Programming and Measurement (RS-232/485, USB, LAN, GPIB) |
|||||||
Model |
|
PSU |
6-200 |
12.5-120 |
20-76 |
40-38 |
60-25 |
Output voltage programming accuracy |
0.05% + |
mV |
3 |
6.25 |
10 |
20 |
30 |
Output current programming accuracy |
0.2% + |
mA |
200 |
120 |
76 |
38 |
25 |
Output voltage programming resolution |
|
mV |
0.2 |
0.4 |
0.7 |
1.3 |
2 |
Output current programming resolution |
|
mA |
6 |
4 |
2.5 |
1.2 |
0.8 |
Output voltage measurement accuracy |
0.1% + |
mV |
6 |
12.5 |
20 |
40 |
60 |
Output current measurement accuracy |
0.2% + |
mA |
400 |
240 |
152 |
76 |
50 |
Output voltage measurement resolution |
|
mV |
0.2 |
0.4 |
0.7 |
1.3 |
2 |
Output current measurement resolution |
|
mA |
6 |
4 |
2.5 |
1.2 |
0.8 |
Input Characteristics |
|||||||
Model |
|
PSU |
6-200 |
12.5-120 |
20-76 |
40-38 |
60-25 |
Norminal input rating |
|
|
100Vac to 240Vac, 50Hz to 60Hz, single phase |
||||
Input voltage range |
|
|
85Vac ~ 265Vac |
||||
Input frequency range |
|
|
47Hz ~ 63Hz |
||||
Maximum input current |
100Vac |
A |
21 |
||||
|
200Vac |
A |
11 |
||||
Inrush current |
|
|
Less than 50A. |
||||
Maximum input power |
|
VA |
2000 |
||||
Power factor |
100Vac |
|
0.99 |
||||
|
200Vac |
|
0.98 |
||||
Efficiency (*13) |
100Vac |
|
77 |
82 |
83 |
84 |
84 |
|
200Vac |
|
79 |
85 |
86 |
87 |
87 |
Hold-up time |
|
|
20ms or greater |
||||
Interface Capabilities |
|||||||
Model |
|
PSU |
6-200 |
12.5-120 |
20-76 |
40-38 |
60-25 |
USB |
|
|
TypeA: Host, TypeB: Slave, Speed: 1.1/2.0, USB Class: CDC(Communications Device Class) |
||||
LAN |
|
|
MAC Address, DNS IP Address, User Password, Gateway IP Address, Instrument IP Address, Subnet Mask |
||||
GPIB |
|
|
SCPI - 1993, IEEE 488.2 compliant interface |
||||
RS-232/RS-485 |
|
|
Complies with EIA232D / EIA485 Specifications |
||||
Environment Conditions |
|||||||
Model |
|
PSU |
6-200 |
12.5-120 |
20-76 |
40-38 |
60-25 |
Operating temperature |
|
|
0˚C to 50˚C |
||||
Storage temperature |
|
|
-25˚C to 70˚C |
||||
Operating humidity |
|
|
20% to 85% RH; No condensation |
||||
Storage humidity |
|
|
90% RH or less; No condensation |
||||
Altitude |
|
|
Maximum 2000m |
||||
Environment Conditions |
|||||||
Model |
|
PSU |
6-200 |
12.5-120 |
20-76 |
40-38 |
60-25 |
Weight |
main unit only |
kg |
Less than 8.7kg |
||||
Dimensions |
(W×H×D) |
mm3 |
423×43.6×447.2 |
||||
Cooling |
|
|
Forced air cooling by internal fan. |
||||
EMC |
|
|
Complies with the European EMC directive 2004 /108/EC for Class A test and measurement products. |
||||
Safety |
|
|
Complies with the European Low Voltage Directive 2006 /95/EC and carries the CE-marking. |
||||
Withstand voltage |
|
|
AC to Chassis: 1500Vac/1min |
||||
Insulation resistance |
|
|
Chassis and output terminal; chassis and AC input; AC input and output terminal: 100MΩ or more (DC 500V) |
||||
|
|
|
|
|
|
|
|