MI 3101 EurotestAT

Key features

  • Autosequences: Testing of electrical installation safety with AUTO SEQUENCE ® is up to 5 times faster compared to traditional installation tester.
  • All-in-one insulation: insulation tests between L-N, L-PE and N-PE can be performed simultaneously in less than 10 seconds.
  • Structure building: a structure of the installation (up to 10 levels) can be built either using the software (which can then be sent to the instrument) or directly on the tester so that test results are always saved on the correct circuit.
  • Barcode reading support: reading of data from barcode labelled installation structure elements for fast naming of memory locations on the field.
  • Fuse location: function enables the locating of fuses / wires / faults with the help of the optional A 1191 Fuse locator.
  • Earth resistance measurement: Unit can perform 3-wire earth resistance testing and specific earth resistance measurement.
  • Downloadable: downloads via RS232 or USB cable directly to the PC with the help the software included in the standard set.
  • Help screens: instrument comes complete with built-in help screens for referencing on site.
  • Built-in fuse tables: this unique feature allows automatic evaluation of the line / loop impedance compared to the regulations.
  • Online voltage monitoring: monitors all 3 voltages in real-time.
  • Upgradeable: if changes occur to the regulations, upgrades can be made to the firmware to keep the instrument up to date.
  • Polarity swap: automatic polarity reversal on continuity test.
  • Insulation range: wide range of insulation test voltages from 50 V to 1000 V, reading up to 1000 MΩ.
  • Trip Lock function: Zs (RCD) function performs a loop impedance test without tripping the RCD.
  • Multi-system testing: tests on TT, TN, IT and 115 V systems.
  • Wide frequency range: 14 ... 500 Hz.
  • Built-in charger & rechargeable batteries: unit has a built-in charging circuit and comes complete with a set of rechargeable NiMH batteries.
  • RCD auto: automated RCD testing procedure significantly reduces test time.
  • B type RCD testing is supported.
  • BT connectivity: it enables BT communication with Android tablets and smart phones via optional BT dongle.
  • PC SW EuroLink PRO included in the standard set enables downloading of test results and parameters and creation of test reports.

  • Share on

The MI 3101 EurotestAT is the first installation safety tester with automated testing based on patented technology AUTO SEQUENCE ®. This remarkable instrument is equipped with a number of unique features including “All-in-one” installation safety testing, integrated characteristics of fuses and RCDs (including B type), PASS / FAIL evaluation of test results and 10-level memory structure. Besides the EurotestAT has additional features like fuse / wire locating facility, specific earth resistance measuring function and built-in battery charger. All the results can be quickly saved and referenced on the instrument and then downloaded via the EuroLink PRO software, included in the standard set, to the computer for evaluation and report generation after testing. The MI 3101 EurotestAT performs continuity, insulation, RCD, loop, line, voltage, frequency, earth resistance testing and phase sequence tests required by the EN 61557 standard.

ket Function is supported
ket Function is not supported
ket Function is optional

 


MI 3101 EurotestAT

 

 

 

 

Extra Features AUTOSEQUENCE ® AUTOSEQUENCE profile ket
AUTOSEQUENCE programmable
PASS/FAIL System Evaluation
Custom Visual/Functional Inspection
Advanced User Interface Graphical Help Menus
Programmable Memory Structure
Multi-level Memory Organiser
Auto Test AUTO TN (U, Zln, Zlpe, Rpe)
AUTO TN/RCD (U, Zln, Zs, Rpe)
AUTO TT (U, Zln, Zs, Uc)
Automatic test sequence Multitest sequence
Main Features Voltage Frequency
Voltage Monitoring
Voltage TRMS
Three Phase 3-Phase system (Phase SEQUENCE)
Insulation Resistance Autotest Insulation L-PE, N-PE, L-N
Test Voltage 50 V
Test Voltage 100 V
Test Voltage 250 V
Test Voltage 500 V
Test Voltage 1000 V
Test of IMD
Automatic Discharge
Leakage Current ISFL: L1,L2 (First Fault Leakage)
Z Line / Loop Impedance Zline L-L, L-N Ipsc - 3 Wire
Zloop L-PE, Ipfc - 3 Wire
Zs (rcd) - 3 Wire
Zref, ΔU%
Fuse Tables
Test Current > 300A 4-wire
Max. Ipfc = 20kA
Zline/loop mOhm high precision
RCD RCD type AC
RCD type A
RCD type F
RCD type B
RCD type B+
RCD Uc
RCD I Ramp
RCD Auto
RCD 3-Phase
RCD-S (Selective)
RCD (t)
Earth / Ground Resistance Earth Resistance 2-wire
Earth Resistance 3-wire
Wenner 4-wire Specific Earth Resistance
Additional Features Hand-Held Hand-Held
Display LCD
Back Light
PASS / FAIL Indicators PASS / FAIL Indicators
Mains Supply / PE Check Mains Supply / PE Check
Keyboard QWERTY Keyboard
Connectivity Communication Port USB
Built-in Bluetooth
Android Application
Communication Port RS232 - PS/2
Memory Downloadable
Internal memory
Uploadable
Printing and scanning QR-Code Printing / Scanning
Power Supply Battery Powered
Rechargeable Batteries in standard delivery
Graphical user interface Graphical on Line Help
Special Accessories Battery Charger Battery Charger
Pasive 3-Phase Adapter Pasive 3-Phase Adapter
Active Euro Checkbox Active Euro Checkbox
Active Ring Adapter EASYswitch Active Ring Adapter EASYswitch (UK only)
Tip Commander Tip Commander
Plug Commander Plug Commander
PC Software Package Report creation
PC Software Package
Professional reporting
Adapter for specific resistance ρ ρ adapter
Cable Locator Cable Locator
Connectivity accessories BT dongle
Standards Applied IEC 60364 IEC 60364-6
IEC 60364-4-41
IEC 60755 IEC 60755
IEC 61008 IEC 61008
IEC 61009 IEC 61009
IEC 61557 IEC 61557-1
IEC 61557-2
IEC 61557-3
IEC 61557-4
IEC 61557-5
IEC 61557-6
IEC 61557-7
IEC 61557-10
AS / NZ 3760 AS / NZ 3760
AS / NZ 3018 AS / NZ 3018
AS / NZ 3017 AS / NZ 3017
VDE 0413 VDE 0413
VDE 0100 VDE 0100
HD 384 HD 384
BS 7671 BS 7671 17th Edition


Loading...